VENTURA TP Nickel Cadmium Batteries
Brand:Ventura AERO
Product Type:Industrial Batteries
Introduction
VENTURA TP Nickel Cadmium batteries are designed for power supply systems requiring load durations between 1 and 10 hours.They are suitable for various operational modes:battery operation mode(charger disconnected during discharge),response mode(battery switched into circuit at power failure),and standby mode(battery permanently connected to the charging source and load).These batteries are robust and resistant to deep discharge and mechanical stress.Key application areas include power stations,substations,UPS,industrial systems,traffic control,and emergency power supply systems.
Construction Details
Positive Electrode:Pocket plate
Negative Electrode:Pocket plate
Separation:Perforated separator
Casing Material:Polystyrene,impact resistant
Electrolyte:Potassium hydroxide,density 1.19 kg/l
Terminal Design:Solid nickel-plated steel posts with bolted connection
Pole Screw:Metric threaded,nickel-plated steel screw
Connectors:Solid nickel-plated copper connector
Vent Plugs:Gas drying vent plug
Features
Single cells with a nominal voltage of 1.2 V
High power performance during discharge
High energy output at low temperatures
Charging and Operation
Charging:Float charge voltage:1.40 V/cell;Boost charge voltage:1.55-1.65 V/cell
Recommended Range of Operation:-20°C to+45°C(preferred value 20°C)
Product Standard:DIN 40771
Cell Correspondence:TP cells correspond with KPM-P type cells according to EN 60623 and IEC 60623.
Technical Data
The electrical values shown in the table relate to loadings from a fully charged condition at an ambient temperature of+20°C.Height includes connectors(*).
| Type Designation | Capacity (Ah) | Internal resistance (mOhm/cell) | Short circuit current (A) | Dimensions (mm) | Weight (kg) | Poles | Type Designation | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| C10 | C5 | C1 | C3 | C2 | C1 | C1 | L | W | H* | cell | w. e. lyte | e. lyte | |||||
| TP 10 | 10 | 10.5 | 10.4 | 10.3 | 9.9 | 8.2 | 14.01 | 85 | 85 | 46 | 85 | 1.03 | 0.32 | 2 x M 10 | TP 10 | ||
| TP 18 | 18 | 19.0 | 18.6 | 18.5 | 17.8 | 14.8 | 7.79 | 154 | 46 | 85 | 257 | 1.41 | 0.49 | 2 x M 10 | TP 18 | ||
| TP 24 | 24 | 25.5 | 25.1 | 25.0 | 24.0 | 20.0 | 5.84 | 205 | 46 | 85 | 257 | 1.51 | 0.39 | 2 x M 10 | TP 24 | ||
| TP 30 | 30 | 32.0 | 31.7 | 31.5 | 30.2 | 25.2 | 4.68 | 256 | 46 | 85 | 257 | 1.64 | 0.37 | 2 x M 10 | TP 30 | ||
| TP 40 | 40 | 42.5 | 42.2 | 42.0 | 40.3 | 33.6 | 3.52 | 340 | 85 | 85 | 257 | 2.68 | 0.88 | 2 x M 10 | TP 40 | ||
| TP 55 | 55 | 58.0 | 57.8 | 57.5 | 55.2 | 46.0 | 2.57 | 466 | 85 | 85 | 257 | 2.97 | 0.67 | 2 x M 10 | TP 55 | ||
| TP 65 | 65 | 69.0 | 68.3 | 68.0 | 65.3 | 54.4 | 2.24 | 534 | 53 | 134 | 400 | 5.01 | 1.29 | 2 x M 20 | TP 65 | ||
| TP 75 | 75 | 79.5 | 78.9 | 78.5 | 75.4 | 62.8 | 1.96 | 610 | 53 | 134 | 400 | 5.16 | 1.22 | 2 x M 20 | TP 75 | ||
| TP 90 | 90 | 95.5 | 95.0 | 94.5 | 90.7 | 75.6 | 1.57 | 763 | 69 | 134 | 400 | 6.34 | 1.82 | 2 x M 20 | TP 90 | ||
| TP 110 | 110 | 117 | 116 | 116 | 111 | 92.4 | 1.28 | 936 | 69 | 134 | 400 | 6.67 | 1.57 | 2 x M 20 | TP 110 | ||
| TP 125 | 125 | 133 | 132 | 131 | 126 | 105 | 1.13 | 1059 | 70 | 164 | 400 | 7.83 | 2.06 | 2 x M 20 | TP 125 | ||
| TP 140 | 140 | 148 | 148 | 147 | 141 | 118 | 1.01 | 1185 | 70 | 164 | 400 | 8.00 | 1.80 | 2 x M 20 | TP 140 | ||
| TP 165 | 165 | 175 | 173 | 173 | 166 | 138 | 0.86 | 1382 | 108 | 164 | 400 | 10.70 | 3.69 | 2 x M 20 | TP 165 | ||
| TP 185 | 185 | 196 | 195 | 194 | 186 | 155 | 0.77 | 1542 | 108 | 164 | 400 | 11.10 | 3.41 | 2 x M 20 | TP 185 | ||
| TP 200 | 200 | 212 | 211 | 210 | 202 | 168 | 0.71 | 1671 | 108 | 164 | 400 | 11.30 | 2.90 | 2 x M 20 | TP 200 | ||
| TP 230 | 230 | 243 | 242 | 242 | 231 | 193 | 0.62 | 1910 | 108 | 164 | 400 | 11.80 | 2.80 | 2 x M 20 | TP 230 | ||
| TP 275 | 275 | 291 | 289 | 289 | 277 | 230 | 0.53 | 2232 | 164 | 158 | 402 | 16.40 | 5.20 | 2 x M 20 | TP 275 | ||
| TP 315 | 315 | 333 | 332 | 331 | 317 | 264 | 0.44 | 2676 | 164 | 158 | 402 | 18.20 | 4.80 | 4 x M 20 | TP 315 | ||
| TP 380 | 380 | 402 | 400 | 399 | 381 | 317 | 0.37 | 3214 | 164 | 158 | 402 | 20.10 | 3.80 | 4 x M 20 | TP 380 | ||
Installation
VENTURA TP cells are suitable for installation on racks or in cabinets.The batteries can be assembled in crates for mobile use or for special applications.Special racks are available for use in earthquake zones.Cells must be operated in accordance with the safety requirements stated in EN 50272-2.
Cell Arrangement Diagrams
The following descriptions represent typical cell arrangements for different TP series models:
TP 10-TP 30;TP 65-TP 230:These diagrams illustrate common configurations for these series,showing the overall length(L),width(W),and height(H,including connectors)of the cell arrangements.
TP 40-TP 55:Similar to the above,these diagrams depict typical cell arrangements for the TP 40 to TP 55 series,indicating dimensions L,W,and H(including connectors).
TP 275:This diagram shows the typical cell arrangement for the TP 275 model,detailing dimensions L,W,and H(including connectors).
TP 315-TP 380:These diagrams illustrate typical cell arrangements for the TP 315 to TP 380 series,specifying dimensions L,W,and H(including connectors).
General Notes and Certification
All dimensions and weights shown are subject to usual manufacturing tolerances.Electrical values are approximate.The right is reserved to make alterations with a view to technically improved execution without prior notice.
Certification:The manufacturing process adheres to DIN EN ISO 9001 standards.